STAAD.Pro Physical Modeler Help

Create: Wind Load Definition dialog

This dialog is used to add either code-prescribed parameters for wind loads or a wind intensity profile.

Opens when the Wind tool in the Create Load Definitions group is selected on the Catalog ribbon tab.

Wind tab

SettingDescription
Name Type a descriptive name for the wind load definition.
Code Select the code for entering wind data:
  • Custom – used to enter data pairs of wind pressure at given heights
  • SP 20.13330 – used to enter wind load parameters for both static and dynamic wind loads per the SP 20.13330 2016 code
  • ASCE 7 - used to enter wind load parameters for wind loads per the ASCE code
Version For code wind loads, select the edition of the code to use from the drop-down list.
Properties Used to enter code parameters for a wind definition. Refer to the SP 20.13330.2016 or ASCE 7 sections below for parameter details.
Intensity Vs Height (For Custom wind definitions) Click in the field to open the Height vs. Pressure data table. Enter pairs of data for wind pressure at a given height (in the current units).

Int cells – wind intensities (pressures) in force/area. Up to 100 different intensities can be defined in the input file per type.

Height cells – corresponding heights in global vertical direction, measured in terms of actual Y (or Z for Z UP ) coordinates up to which the corresponding intensities occur.

SP 20.13330.2016 Wind Load Parameters

For SP 20.13330.2016 wind load definitions, the following parameters apply.

SettingDescription
Pressure the characteristic value of wind pressure, always positive
Terrain
terrain roughness category:
  1. Coastal Zone.
  2. Urban Zone.
  3. Large City.
Classification

Region Wind region as per clause 11.5 of SNiP 2.01.07-85* 2016. This is used to determine the wind pressure in determine the dynamic wind component.
Delta
logarithmic decrement of oscillations, Delta (see table 11.5 - Section 11.1.8 for the definition). Typically values are:
  • 0.15 for steel towers, masts, lined chimneys, column means including the ones on the reinforced concrete pedestals
  • 0.3 for reinforced concrete and stone structures as well as for buildings with steel framework if there are walling structures
Select Configuration
The building configuration as defined in SNiP 2.01.07–85 "Loads and Actions":
  • 0. Prismatic building structure - Rectangular building- Outstanding architectural details on the left façade.
  • 1. Prismatic building structure - Rectangular building- Both side façades are smooth
  • 2. Prismatic building structure - Rectangular building- Outstanding architectural details on the right façade
  • 3. Prismatic building structure - Rectangular building- Outstanding architectural details on both side façades
  • 4. Prismatic building structure - Rectangular building- Triangular building
  • 5. Prismatic building structure - Rectangular building- Rhombic building
  • 6. Prismatic building structure - Rectangular building- Number of vertices of polygonal building, not more than 12
  • 7. Prismatic building structure - Less than 3 — rectangular building
  • 8. Prismatic building structure - 3 — triangular
  • 9. Prismatic building structure - 4 — rhombic
  • 10. Prismatic building structure - More than 4 — polygonal
  • 11. Framed RC structure
  • 12. Lattice steel structure

ASCE 7 Wind Load Parameters

For wind load definitions per ASCE 7 Minimum Design Loads for Buildings and Other Structures 2010 or 2016 editions, the following parameters apply.

SettingDescription
Properties
SettingDescription
Building Classification Category Select the building classification category, based on the nature of occupancy, as obtained from Table 1.5-1 in ASCE 7-10 /16.

Category can be I, II, III or IV.

Basic Wind Speed Specify a basic wind speed as described in section 26.5.1 of ASCE 7-10 / 16, along with units.
Height above sea level (For 2016 only) Type the height above sea level for the base of the structure, zg in Table 26.9-1, in the selected units. This is used to calculate the ground elevation factor, Ke

.

Exposure Category Select an exposure category per section 26.7.3 of ASCE 7-10 / 16.
Structure Type

Select the type or structure that best fits the model from the following:

  • Building Structures
  • Chimney, Tank and Similar Structures
  • Solid Signs
  • Open Signs
  • Latticed Framework
  • Trussed Tower
Note: The following dialog section updates to reflect the selection for this parameter.
Consider Wind Speed-up over Hills or Escarpment? Select Yes to consider wind speed-up over a hill or an escarpment and No to ignore it.

If there are isolated hills and escarpments that constitute abrupt changes in the general topography, the increase in speed can be considered per section 26.8.1 of ASCE 7-10 / 16.

Type of Hill or Escarpment Select the type of hill, ridge or escarpment on which the structure is located, based on Figure 26.8-1 of ASCE 7-10 / 16. The options available are:
  • 2-D Ridge
  • 2-D Escarpment
  • 3-D Axisymmetrical
Height of Hill or Escarpment (H) Specify the height of the hill or escarpment relative to the upwind terrain (H in Figure 26.8-1 of ASCE 7-10 / 16).
Distance upwind of crest (Lh) Specify the distance upwind of crest to where the difference in general elevation is half the height of the hill or escarpment (Lh in Figure 26.8-1 of ASCE 7-10 / 16).
Distance from the crest to the building (x) Specify the distance from the crest to the building site.  A negative value signifies the distance is in the downwind direction (x in Figure 26.8-1 of ASCE 7-10 / 16).
Main Building Data For Structure Type of Building Structures.
SettingDescription
Building Height (h)

Specify the height above ground to the highest point on the roof surface, along with units.

Building Length along the direction of Wind (L)

Length of building measured along the direction of wind, along with units.

Building Length Normal to the direction of Wind (B)

Length of building measured normal to the direction of wind, along with units.

Building Natural Frequency

Specify the natural frequency of the building to calculate gust effect factor.

Structure Behavior For buildings with a natural frequency of less than 1Hz, select if the structure is Rigid or Flexible. This determines the method of calculation used for the gust effect factor per section 26.9 of ASCE 7-10 or section 26.11 of ASCE 7-16.
Building Damping Ratio

Specify the damping ratio to calculate Gust Effect Factor.

Enclosure Classification Select the building enclosure classification per section 26.10 of ASCE 7-10 or section 26.12 of ASCE 7-16:
  • Open Building
  • Partial Enclosed
  • Enclosed Building
  • Partially Open (ASCE 7-16 only)
Specify Kzt Check this option if you want to directly specify the topographic factor value for wind speed-up, Kzt. Otherwise, the program-calculated value is used.
Specify Kd Check this option if you want to directly specify the directionality factor, Kd. Otherwise, the value from Table 26.6-1 of ASCE 7-10 / 16 is used based on the selected structure type.
Specify Ke Check this option if you want to directly specify the ground elevation factor, Ke. Otherwise, the factor is calculated per Table 26.9-1 of ASCE 7-16.
Chimney, Tank and Similar Structures

The following parameters are specific to chimney, tank, and similar structures. Other parameters are as described above.

SettingDescription
Height (h) Height of the structure as defined by the term "h" in Figure 29.5-1 of ASCE 7-10 or Figure 29.4-1 of ASCE 7-16.
Least Horizontal Dimension (W)

Smaller of the plan dimensions. In case the cross section of the structure in plan is circular, the diameter needs to be specified.

Horizontal Cross-Section Type

This is the cross section of the structure in plan as defined in Figure 29.5-1 of ASCE 7-10 or Figure 29.4-1 of ASCE 7-16. For ASCE 7-10, the available options include square with wind being normal to face or acting along the diagonal, hexagonal, octagonal and round. For ASCE 7-16, the available options include square with wind normal to face or acting along the diagonal, hexagonal axisymmetric, hexagonal non-axisymetric, round axisymmetric, and round non-axisymmetric.

Depth of protruding elements such as ribs and spoilers (D') For round type cross sections, depth of protruding elements need to be defined which is a measure of the surface roughness as indicated in Figure 29.5-1 of ASCE 7-10 or Figure 29.4-1 of ASCE 7-16.
Solid Sign Data The following parameters are specific to solid sign and wall structures. Other parameters are as described above.
Note: The program does not calculate for return corners on solid signs or walls.
SettingDescription
Height (h) This is used for calculating the height to width ratio as defined by the term "h" in Figure 29.4-1 of ASCE 7-10 or Figure 29.3-1 of ASCE 7-16.
Horizontal Dimension of Sign (M) Horizontal dimension of the solid sign as defined by the term "B" in Figure 29.4-1 of ASCE 7-10 or Figure 29.3-1 of ASCE 7-16.
Vertical Dimension of Sign (N)

Vertical dimension of the solid sign as defined by the term "s" in Figure 29.4-1 of ASCE 7-10 or Figure 29.3-1 of ASCE 7-16.

Note: For signs at the ground level, the height (h) and vertical dimension (N) should both be specified the same value.
Open Sign & Framework Data The following parameters are specific to open sign and framework structures. Other parameters are as described above.
SettingDescription
Height (h) Height of the sign.
Width (B) Horizontal dimension of the sign.
Ratio of Solid Area to Gross Area Ratio of solid area to gross area as indicated by the term "" in Figure 29.5-2 of ASCE 7-10 or Figure 29.4-2 of ASCE 7-16.
Orientation of the members exposed to wind The type of member surfaces which are exposed to wind. Select flat-sided members (Flat) or Rounded members as per Figure 29.5-2 of ASCE 7-10 or Figure 29.4-2 of ASCE 7-16. This value is given as a ratio between zero and one.
Diameter of the typical round member For Rounded members, specify the outer diameter typical for the exposed members as indicated by the term "D" in Figure 29.5-2 of ASCE 7-10 or Figure 29.4-2 of ASCE 7-16, along with units.
Trussed Tower Data The following parameters are specific to trussed tower structures. Other parameters are as described above.
SettingDescription
Height (h) Height of the trussed tower.
Width (B) Horizontal dimension of the trussed tower.
Ratio of Solid Area to Gross Area of Tower face (%) Ratio of the solid area to gross area of one tower face as indicated by the term "" in Figure 29.5-3 of ASCE 7-10 or Figure 29.4-3 of ASCE 7-16. This value is given as a percentage.
Horizontal Cross Section The type of cross section of the tower in plan as defined in Figure 29.5-3 of ASCE 7-10 or Figure 29.4-3 of ASCE 7-16. The available options include Square and Triangle.
Building Design Pressure Used for the calculation of the design pressure intensity for building structures.
SettingDescription
Building Wall to generate Wind Load on

Select the side of the structure, with respect to wind direction, for which you want to generate a wind load. The pressure will be calculated as per Figure 27.4-1 of ASCE-7-2010 or as per equation 27.3-1 and 27.3-2 of ASCE 7-16, based on the code selection made in the Properties section. The relevant equation will also be displayed below.

  • Windward - Used to generate the design wind pressure for the windward side.
  • Leeward - Used to generate the design wind pressure for the side wall.
  • Side Wall - Used to generate the design wind pressure for the side wall.
Note: The pressure profile for each of the building walls has to be individually determined under a unique load type number. Thus, generating the profile for the three sides of the building constitutes three separate steps and thus, three separate types. Each type can then be applied with one load case or separate load cases and then applied in the relevant direction with the appropriate direction factor. Examples illustrating wind load generation can be found in the examples manual.
Specify G

Select this option to specify a gust effect factor value, G.

If not selected, the Gust effect factor is calculated and displayed. For rigid structures (natural frequency ≥ 1Hz), the gust effect factor is calculated as per equation 26.9-6 for ASCE 7-10 or equation 26.11-9 for ASCE 7-16 . For flexible structures (natural frequency < 1Hz), the gust effect factor is calculated section 26.9-10 for ASCE 7-10 or section 26.11-10 for ASCE 7-16.

Specify Cp

Select this option to specify a wall pressure coefficient value, Cp.

If not selected, the wall pressure coefficient is calculated and displayed. The wall pressure coefficient is calculated as per as per Figure 27.4-1, 27.4-2 and 27.4-3 of ASCE 7-10. For ASCE 7-16, the wall pressure coefficient is calculated as per Figure 27.3-1.

Specify (GCpi)

Select this option to specify an internal pressure coefficient value, (GCpi).

If not selected, the internal pressure coefficient is calculated and displayed. The internal pressure coefficient is calculated as per Figure 27.4-1, 27.4-2 and 27.4-3 of ASCE 7-10. For ASCE 7-16, the internal pressure coefficient is calculated as per Figure 26.13-1.

Intensity vs Height Click in the field to display the Height vs. calculated Pressure data table. The pressure values are calculated at regular intervals up to the building or structure height entered.
Design Pressure (Other Structure)
SettingDescription
Specify Cf

Select this option to specify a force coefficient value used for structures other than buildings. If not selected, the force coefficient is calculated as per Figure 29.4-1, 29.5-1, 29.5-2 or 29.4-3, depending on the non-building structure type selected.

The force coefficient is used for the calculation of the design pressure.

Exposure tab

Used to specify exposure factors.
SettingDescription
Exposure Used to enter exposure factors. A value of 1.0 means that the wind force may be applied on the full influence area associated with the joint(s) if they are also exposed to the wind load direction. Limit: 99 factors.
Note: Note any joint does not have an exposure assigned, the exposure will be taken as 1.0.