RAM Concrete Column uses the dead load and live skip loading results from Concrete Analysis in conjunction with the RAM Frame lateral analysis results, where applicable, to create a set of design points for each column using the defined load combinations. These design points are a set of Axial Forces, Major Moments, Minor Moments, Major Shears, Minor Shears and Torsion at the top and bottom of the column for each load combination and pattern (see Section 2.3.4).
The column capacity is based on a biaxial interaction surface that identifies the Major and Minor Moment limits for any given axial load.
Maximum Column Axial Capacity
The maximum axial compression capacity of the column is limited to:
ϕbPn(max) = 0.85ϕc[0.85f'c(Ag - As) + fyAs] | Equation ACI 10-1 |
The maximum axial tension capacity of the column is calculated using only the reinforcement capacity:
Column Flexural Capacity
Capacity points on the interaction surface are calculated using the reinforcement force and concrete section compression force assuming a C.S. Whitney Equivalent Rectangular Stress Distribution as outlined in ACI 10.2.7.
P = Cc + Cs + Ts | Equation 4-2 |
Reinforcement tension force is:
where
Fs | = |
Equation 4-3
|
Reinforcement compression force is:
Cs = Σ(Fs - 0.85f'c)As | Equation 4-4 |
Concrete compression force is:
Cc = 0.85f'cab | Equation 4-5 |
where
a | = |
Equation 4-6
|
Section moment capacity is:
Ms = ΣTsLs + ΣCsLs | Equation 4-8 |
Whitney equivalent stress distribution
The above calculation is performed for the major and minor direction of the column section, as well as all intermittent angles at the specified increment. The result is a full 3-D interaction surface. The interaction surface between the major and minor directions is calculated explicitly and is not based on an approximate method like the PCA Method outlined in Reference # 4.
The interaction surface is then reduced by the following factors:
For ϕcPn(max) ≥ Pu > 0.10f'cAg | ACI-9.3.2.2 |
If fy ≤ 60 ksi and (h - d - ds)/h ≥ 0.70 | ACI-9.3.2.2 |
then when 0.10f'cAg ≥ Pu ≥ 0.0, ϕ is linearly increases from ϕc to ϕb | |
Otherwise when:
min(0.10f'cAg, ϕcPb) ≥ Pu ≥ 0.0 | ACI-10.3.3 |
ϕ is linearly increases from ϕc to ϕb | |
For Pu < 0.0, ϕ = ϕb = 0.90 | |
Interaction Diagram Check
Each data point is checked against the interaction surface to confirm that it is inside the surface. The factored moments Mu major, Mu minor are converted to and checked against the interaction surface at the angle
The load to capacity ratio Ld/Cap is calculated in one of two ways based on the axial load.
When Pu > min (0.1f'cAs, ϕcPb) | |
Ld/Cap = max(Pu/ϕcPn max, Muθ/ϕcMnθ) | |
Ld/Cap = max(Pu/ϕbPn min, Muθ/ϕbMnθ) | |
when
min(0.1f'cAs, ϕcPb) > Pu > 0 | |
ϕ is linearly increases from
ϕc to
ϕb
Column Interaction Diagram at Angle θ
Longitudinal Reinforcement Spacing
The longitudinal reinforcement spacing limit is checked using:
smin = min(1.5db, 1.5 in.) | ACI-7.6.3 |
smax does not have a code limit other than the requirements for bracing using ties.
The user defined spacing limits may control if they are more restrictive than the code prescribed limits.
Longitudinal Reinforcement Ratio
The area of longitudinal reinforcement is subject to the following limits:
0.01 ≤ ρ ≤ 0.08 | ACI-10.9.1 |
ρ ≤ 0.75ρb when ϕPn ≤ min(0.10f' cAg, ϕPb) | ACI-10.3.3 |
where
ρb
| = |
ACI-10.3.2
|
β1
| = |
ACI-10.2.7.3
limited by 0.65 ≤ β1 ≤ 0.85
|
Note: The design check does not account for the final provision of ACI 318-95 and 99, Section 10.3.3, which allows the reinforcement in compression to not be reduced by 0.75. This will cause some columns to have a Design Warning generated because all the reinforcement in the column is reduced by the 0.75 factor. In most cases the engineer will be able to make a judgment on whether at least one side of the reinforcement will be in compression (which in most cases is a valid assumption), in which case a quick hand calculation will confirm that the provision of 10.3.3 will be met and the Design Warning can be disregarded.