Modifications to Seismic Provisions

There are two substantial changes that have been made to Chapter 21 in ACI 318-08. First, the sections of Chapter 21 have been reorganized so that the requirements for "ordinary", "intermediate", and "special" systems are presented in this respective order throughout the chapter. As a result, the numerical section corresponding to a given provision has changed for the majority of the sections. Second, the concept of a seismic design category has been introduced to the provisions. The individual provisions of Chapter 21 that a building must satisfy are now dependent on both the structural category (ordinary, intermediate, or special) and the seismic design category.

The following table provides a summary of the code sections a building must satisfy based on frame type.
Table 1. Required Chapter 21 Code Sections by Frame Type
Frame Type Applicable Code Sections
OMRF 21.2
IMRF 21.3
SMRF (cast-in-place)

1.3 through 21.1.7

21.5 through 21.7

SMRF (precast)

1.3 through 21.1.7

21.5 through 21.8

OSW None
ISW (precast) 21.4
SSW (cast-in-place)

1.3 through 21.1.7

21.9

SSW (precast)

1.3 through 21.1.7

21.10

The following table provides a summary of the code sections a building must satisfy based on seismic design category.
Table 2. Required Chapter 21 Code Sections by Seismic Design Category
Seismic Design Category Applicable Code Sections
A None
B 21.1.2
C 21.1.2, 21.1.8
D, E, and F 21.11 through 21.13