RAM Structural System Help

Column Torsion Check

The torsion check is provided to identify columns that require torsion reinforcement.

Torsional reinforcement is not required when:
T u < ϕ f c ( A c p 2 p c p ) = ϕ T T c ACI 11.6.1
where
Acp
=
hb
pcp
=
2(h + b)

In addition, if the beam/column has axial load an additional check is performed:

T u < ϕ T n ACI 11.6.1(c)
T n = f c ( A c p 2 p c p ) 1 + N u 4 A g f c
N u 4 A g f c < 1 n

ACI 11.6.2.1 states that whenϕTTc ≥ Tu torsional reinforcement is required in accordance with ACI 11.6.3 through 11.6.6. The torsion check will generate a design warning when torsion reinforcement is required.

Note: ACI 11.6.3.1 is not checked for columns to see if the column cross-sectional dimensions will permit torsional reinforcement.