RAM Structural System Help

IBC 2000 - 2018

The requirements for Live Load Reduction are given in Section 1607.9, "Reduction in live loads," of IBC 2000, 2003, 2006, and 2009; Section 1607.10 of IBC 2012 and 2015; and Section 1607.11 of IBC 2018. There are two methodologies. The General Method is based on ASCE 7-05, and the Alternate method is based on UBC 97. These options are given in the Criteria > Live Load Reduction command in the RAM Manager. On the Reports, "IBC" is listed as the Building Code when the General method is selected; "IBC Alt" is listed when the Alternate method is selected.

General Live Load Reduction

The General live load reduction methodology is given in IBC 2018 Section 1607.11.1. Note that this is identical to the requirements given in ASCE 7-16. For members for which KLLAT is 400 ft2 or more, the live load may be reduced according to the following formula:
L = L 0 ( 0.25 + 15 K L L A T ) Equation 16-23
where
L
=
the reduced design live load per square foot of area, psf
L0
=
the unreduced design live load per square foot of area, psf
AT
=
the tributary area, ft2
KLL
=
the Live Load element factor from Table 1607.11.1

For members supporting one floor, L shall not be less than 0.50L0 (this is a 50% reduction). For members supporting two or more floors, L shall not be less than 0.40L0 (this is a 60% reduction). To be consistent with the way the Live Load reduction is reported by the program for other Building Codes, the Live Load Reduction value will be computed and given as a percent reduction, rather than as a multiplier.

The Live Load Reduction value is further limited to the user specified maximum, if any.

There is a special provision in the code (IBC 2018 Section 1607.11.1.2 Heavy live loads) for live loads greater than 100 psf. In the program, this type of load is referred to as “Storage” live load and, for such loads a reduction of up to 20% (if allowed by Eq. 16-23) is allowed on members carrying storage load from two or more levels. The user must explicitly designate loads as Storage. Any live load designated by the user as Storage will be treated as explained whether the load is greater than 100 psf or not, and any load not specified by the user as Storage will not be treated as Storage even if it exceeds 100 psf.

Table 1607.11.1 gives values for KLL. Theoretically it is the ratio of the Influence Area to the Tributary Area: K L L = A i A T . Typically the value for columns is 4, and the value for beams is 2. With these values, the equation gives the same reduction values as ASCE 7-95 and ASCE 7-93, which is what has been implemented for BOCA Live Load Reduction. When there are large cantilevered areas contributing to the area supported by the member, the values of 4 for columns and 2 for beams are considered unconservative. The table gives a value of 3 for edge columns with cantilever slabs, 2 for corner columns with cantilever slabs, and 1 for edge beams with cantilever slabs. The Code does not give any indication as to what fits within the definition of cantilever slabs. For example, it does not seem that a column supporting beams that carry a nominal slab edge would need to be included under this classification. The table also specifies a value of 1 for cantilever beams.

The program determines both the tributary area and the influence area for each member. KLL is then calculated:

K L L = A i A T

To conform to the table values, which show integer numbers, the program will round the calculated KLL to an integer value as well. This is done as follows:

  • If KLL is greater than 3.85, it rounds up to 4, otherwise it rounds down to 3.
  • If KLL is greater than 2.85, it rounds up to 3, otherwise it rounds down to 2.
  • If KLLL is greater than 1.85, it rounds up to 2, otherwise it rounds down to 1.

The 0.15 tolerance for rounding up is to avoid unduly penalizing members that carry some nominal slab edge or very short cantilevers.

For loads on the cantilever portion of a cantilever beam, KLL = 1.

KLL is calculated independently for both Reducible Live Loads and Storage Live Loads based on their respective tributary and influence areas.

Alternate Live Load Reduction

An alternate live load reduction methodology is given in IBC 2018 Section 1607.11.2. It is based on the methodology specified by the UBC. Beginning with IBC 2015 a subtle but important change was made, making it identical to the UBC live load reduction method: previous to IBC 2015 the requirement stated that the reduction for horizontal members (i.e., beams) is limited to 40% and the reduction for vertical members (i.e., columns) is limited to 60%. Note that this meant that a column carrying load from only one level could be reduced up to 60%, and a transfer girder carrying load from more than one level could only be reduced up to 40%. Beginning with IBC 2015 the requirements now say that for members receiving load from one level only the reduction is limited to 40% and for members receiving load from two or more levels the reduction is limited to 60%. In prior versions of the program the requirements of the pre-IBC 2015 were implemented but beginning with V17.02 the requirements given in IBC 2015 and later are now used.

For loads specified as Reducible, any member supporting 150 square feet or more of Reducible live load is reduced per Equation 16-24: R = 0.08(A – 150) where A is the tributary area and R is the reduction percent, limited to a maximum of 40% for beams and 60% for columns as explained above. The reduction is further limited to that obtained from Equation 16-25: R = 23.1(1+D/L) where D/L is the ratio of the Dead Load to Live Load, and it is further limited to the user specified maximum, if any.

There is a special provision in the Code (Section 1607.11.2.1) for live loads greater than 100 psf. In the program, this type of load is referred to as ’Storage" live load and, for such loads a reduction of up to 20% (if allowed by Eq. 16-24 and Eq. 16-25) is allowed on members supporting load from two or more floors. The user must explicitly designate loads as Storage. Any live load designated by the user as Storage will be treated as explained whether the load is greater than 100 psf or not, and any load not specified by the user as Storage will not be treated as Storage even if it exceeds 100 psf.

Roof Live Load Reduction

Minimum Roof Live Load is specified in Section 1607.11 Roof Loads, and is given by:

Lr = 20R1R2 (Equation 16-24)

where
Lr
=
the Roof live load per square foot of horizontal projection, psf,
R1
=
a reduction factor based on tributary area, At (sq. ft):

R1 = 1.0 for At ≤ 200 ft2 (Equation 16-25)

R1 = 1.2 - 0.001 At for 200 < At < 600 ft2 (Equation 16-26)

R1 = 0.5 for At ≥ 600 ft2 (Equation 16-27)

where
R2
=
a reduction factor based on slope, F (inches of rise per ft). See Equation 16-28 through 16-30. The slope of the framing is automatically determined and the R2 value is calculated and applied.
Lr
=
limited to the range of 12 psf to 20 psf , which means a reduction of up to 40% is allowed. Note that any value of Roof live load can be input (not necessarily 20 psf) and the program will reduce it by the appropriate factor. For example, if a Roof live load of 30 psf is assigned to a member carrying over 600 square feet of roof area, the load is reduced to 18 psf (i.e., 30 psf times 0.60). To be consistent with the other Building Codes, the Live Load Reduction value is computed and reported as a percent reduction.

The Live Load Reduction value will further be limited to the user specified maximum, if any.