IBC 2003
Section 1609 of IBC 2003 gives wind requirements specifically focused on a simplified procedure acceptable for enclosed, low-rise, simple diaphragm buildings having a height of less than 60 feet. For other types, it refers to Section 6 of ASCE 7-02 where three methods are given: Method 1- Simplified Procedure, Method 2- Analytical Procedure, and Method 3- Wind Tunnel Procedure. Method 2 is further composed of two different provisions: method for Low-Rise Buildings and for Buildings of Any Height.
Among these methods, only Method 2-Analytical Procedure for Buildings of Any Height is implemented into the program. This method is similar to Method 2 - Analytical Procedure of ASCE 7-98/IBC 2000 wind provision. See Section 6 of ASCE 7-02.
In the Loads – Load Cases command the IBC 2003 Wind option is referred to as "ASCE 7-02 / IBC 2003".
Exposure A is not available in ASCE 7-02 / IBC 2003.
Rigid Buildings of All Height
p = q GCp- qi(GCpi) | (Equation 6-17) |
However, it is assumed that internal pressures cancel each other for the main resisting system so that Equation 6-17 is simplified to
p = q GCp |
where
q = 0.00256 KzKztKdV2I | (Equation 6-15) |
and
Kz: Velocity pressure exposure coefficient from Table 6-3. Provided equations in the notes are used
Kzt: Topographic factor. It can be specified by the user or it is obtained from
Kzt= (1+K1K2K3)2 | (Equation 6-3) |
where K1, K2, LH and γ for K3 are entered by the user.
Note that the following limits are checked for these variables: 0.15 ≤ K1 ≤ 0.775, 0.0 ≤ K1 ≤ 1.0 and 2.5 ≤ γ ≤ 4.0 If only Kzt is entered, this value is applied for all heights. Otherwise, its variation with height is considered as given in Equation 6-3.
Kd: Wind directionality factor from Table 6-4. It is taken as 0.85 if specified by user.
V: Basic wind speed from Figure 6-1
I: Importance factor from Table.6-1
G: Gust factor calculated from Equation 6-4. It can be taken as 0.85 if specified by the user.
Cp: External pressure coefficient from Figure 6.6. A value of 0.8 is used for Windward wall and an interpolated value is used for Leeward wall if needed.
Flexible Buildings
p = qGfCp - qiGCpi | (Equation 6-19) |
However, it is assumed that internal pressures cancel each other for the main resisting system so that Equation 6-19 is simplified to
p = q GfCp |
= |
Pressures on parapets for rigid or flexible structures are calculated as follows:
pp= qp GCpn | (Equation 6-20) |
= | ||
= | ||
= |
Section 1609.1.2 of IBC 2003 limits the minimum design wind load to 10 psf for both rigid and flexible buildings and this is also enforced in this implementation.
Building natural frequencies can be entered separately for each direction, or they can be calculated by the program.