Basic straight tension development length is calculated using equation 25.4.2.3. The following factors are used in this equation:
c = cover dimension, vertical distance from the center of the bar to the nearest concrete surface (spacing is not considered)
The term (c + Ktr)/db is never taken greater than 2.5
Ktr is conservatively assumed to be zero
Tension development length of standard hooks is calculated using equation 25.4.3.1. The following factors are used in this equation:
When laying out program reinforcement, RAM Concept first attempts to detail reinforcement without confining reinforcement. The confinement reinforcement required for program or user reinforcement defined with "90 Hook (Confined)" or "180 Hook (Confined)" bar ends must by designed by the user outside RAM Concept .
In accordance with sections 7.7.3.3 and 9.7.3.3, the extension length used for this Code is the maximum of 12db or effective depth of the member, taken as the maximum vertical distance from the center of the reinforcing bar to the farthest concrete surface.
The minimum development length is 12 in for straight bars (25.4.2.1b) and 8db or 6 in for hooks (25.4.3.1b and c).