RAM Concept Help

Code Minimum Reinforcement

  • The structural system (as defined in the design section or design strip segment) is considered (beam, one-way slab, two-way slab).
  • The reinforcement type (as defined in the design section or design strip segment) is considered (PT or RC).
  • The placement of the reinforcement is based on the "min. reinforcement location" selection for the design strip segment or design section:
    • Elevated Slab – Reinforcement is at top near supports and bottom near midspan.
    • Mat Foundation – Reinforcement is at bottom near supports and top near midspan.
    • Tension Face – Reinforcement location is determined by the design moment envelope for the rule set (reinforcement may be required on both faces).
    • Top – Reinforcement is always located at the top of slab (Engineer discretion advised)
    • Bottom – Reinforcement is always located at the bottom of slab (Engineer discretion advised)
    • None – No reinforcement is provided (Engineer discretion advised)
  • Section 18.9.3.2 is not applied (here), as that is a service reinforcement requirement, not a minimum reinforcement requirement (see Service).
  • Section 18.8.3 is not applied to two-way slabs with bonded post-tensioning, even though the code technically requires it.
  • Code Rules are applied as shown in the following table
Table 1. Minimum reinforcement rule mapping
Design System RC

PT

Beam

10.5.1 18.8.3, 18.9.2
One-Way Slab 7.12

18.8.3, 18.9.2

Two-Way Slab 7.12 18.9.3.3 (at supports only)