RAM Concept Help

Design status

Look at design status
  1. Choose Layers > Design Status > Status Plan.

    Design Status: Status Plan.

    This shows OK for all design strips. This means that there are no violations of code limits for ductility, flexural stress and one-way shear. Note that status does not flag excessive deflections.

    There are punching shear status results at each column. You can see these more easily on the dedicated punching plan.

  2. Choose Layers > Design Status > Punching Shear Status Plan.

    RAM Concept has noted "Non-standard section" at six column locations and "OK with SSR" at one column.

    "Non-standard Section" is a warning, not an error. What it means is that at least one of the critical sections that RAM Concept is investigating for that column does not perfectly fit one of the three ACI 318-05 cases: interior, edge and corner. RAM Concept still calculates a stress ratio for non-standard sections. Refer to "Non-Standard Sections: ACI 318 and CSA A23.3" in Chapter 29 for more information.

    Where the unreinforced stress ratio (USR) is less than 1.0, the column’s punching shear is satisfactory without any reinforcement (subject to the comments above concerning "Non-standard section")).

    Stud shear reinforcement is required where RAM Concept reports "OK with SSR".

    If RAM Concept reports "Failed" then SSR does not solve the problem and a thickening is required.

Note: Choose Layers > Design Status > SSR Plan to view the stud shear reinforcement.

Design Status: Punching Shear Status Plan.