RAM Structural System Help

Strength Reduction Factor for Axial-Flexure

The ACI 318-02 implementation in RAM Concrete utilizes Appendices B and C. The ACI 318-05 implementation utilizes the body of the code and does not refer to Appendices B and C.

ACI 318-02 and ACI 318-05 allow the calculation of the strength reduction factor for the design of members subjected to axial-flexural loads according to Appendix C. When this approach is taken, all provisions of Appendices B and C must be used in lieu of the body of the code. This results in the following modifications to the body of the code that are pertinent to RAM Concrete:
  • C.3.2.2 replaces 9.3.2.2. Using this approach, the strength reduction factor for members resisting axial/flexural load is a function of the ultimate axial load acting on the cross section.
  • The load combinations of C.2 replace the load combinations of 9.2.
  • Section B10.3.3 replaces Sections 10.3.3, 10.3.4, and 10.3.5, with the exception of 10.3.5.1.

This is the approach that was taken in the RAM Concrete implementation of ACI 318-02.

The ACI 318-05 implementation in RAM Concrete utilizes Section 9.3, the main body of the code, in calculating strength reduction factors. In ACI 318-05, Section 9.3.2.2, the calculation of the strength reduction factor used for the design of members subjected to a combination of compression-flexure or tension-flexure is dependent on where the section lies relative to a tension-controlled or compression-controlled state. ACI 318-05 defines a compression-controlled section in 10.3.3, and a tension-controlled section in 10.3.4.

Figure below shows the strain condition for a rectangular cross section where the extreme compression fiber has reached the ultimate concrete strain, ε cu.

Cross section illustrating tensile strain in extreme tension fiber, εt, at ultimate concrete strain.

Referring to Figure above, a section is compression-controlled if:

ϵ t ϵ c , limit +
where
ε+c,limit
=
the compression-controlled strain limit, which may be taken as 0.002 for grade 60 steel. RAM Concrete uses ε+c,limit = 0.002 for all situations.

Referring to Figure above, a section is tension-controlled if:

εt≥ 0.005

The following condition represents a transition region between a compression-controlled section and a tension-controlled section.

ε+c,limit ≤ εt ≤ 0.005

Note: RAM Concrete Beam does not consider member axial force during the design and thus all tabulations of c and εt are performed without the consideration of axial force.

Following from these definitions, Section 9.3.2 defines the strength reduction factors for use in member design as follows:

Section 9.3.2.1 – Tension-controlled sections: Φ = 0.90

Section 9.3.2.2 – Compression-controlled sections:
  • Members with spiral reinforcement conforming to 10.9.3: Φ = 0.70
  • Other reinforced members: Φ = 0.65

For sections in the transition region, the following equation is used to calculate the strength reduction factor:

ϕ = 0.65 + ( 0.90 0.65 ) ( ϵ t ϵ c , limit + 0.005 ϵ c , limit + ) 0.90

Section 9.3.2.2 – Shear and torsion: Φ = 0.75

Section 9.3.2.4 – Bearing on concrete (except for post-tensioned anchorage zones and strut-and-tie models): Φ = 0.65