Strength Reduction Factor for Axial-Flexure
The ACI 318-02 implementation in RAM Concrete utilizes Appendices B and C. The ACI 318-05 implementation utilizes the body of the code and does not refer to Appendices B and C.
- C.3.2.2 replaces 9.3.2.2. Using this approach, the strength reduction factor for members resisting axial/flexural load is a function of the ultimate axial load acting on the cross section.
- The load combinations of C.2 replace the load combinations of 9.2.
- Section B10.3.3 replaces Sections 10.3.3, 10.3.4, and 10.3.5, with the exception of 10.3.5.1.
This is the approach that was taken in the RAM Concrete implementation of ACI 318-02.
The ACI 318-05 implementation in RAM Concrete utilizes Section 9.3, the main body of the code, in calculating strength reduction factors. In ACI 318-05, Section 9.3.2.2, the calculation of the strength reduction factor used for the design of members subjected to a combination of compression-flexure or tension-flexure is dependent on where the section lies relative to a tension-controlled or compression-controlled state. ACI 318-05 defines a compression-controlled section in 10.3.3, and a tension-controlled section in 10.3.4.
Figure below shows the strain condition for a rectangular cross section where the extreme compression fiber has reached the ultimate concrete strain, ε cu.
Cross section illustrating tensile strain in extreme tension fiber, εt, at ultimate concrete strain.
Referring to Figure above, a section is compression-controlled if:
where= |
Referring to Figure above, a section is tension-controlled if:
εt≥ 0.005 |
The following condition represents a transition region between a compression-controlled section and a tension-controlled section.
ε+c,limit ≤ εt ≤ 0.005 |
Following from these definitions, Section 9.3.2 defines the strength reduction factors for use in member design as follows:
Section 9.3.2.1 – Tension-controlled sections: Φ = 0.90
- Members with spiral reinforcement conforming to 10.9.3: Φ = 0.70
- Other reinforced members: Φ = 0.65
For sections in the transition region, the following equation is used to calculate the strength reduction factor:
Section 9.3.2.2 – Shear and torsion: Φ = 0.75
Section 9.3.2.4 – Bearing on concrete (except for post-tensioned anchorage zones and strut-and-tie models): Φ = 0.65