Vertical Distribution of Seismic Base Shear

The vertical seismic force (Fx , kip) at a story level is calculated according to the following equation:

Fx = CvxV (12.8-11)

C v x = w x h x k i = 1 n w i h i k
where
Cvx
=
vertical distribution factor
V
=
Base shear (kip)
wi & wx
=
effective seismic weight (kip) at story " i " or " x "
k
=
1.0 for T ≤ 0.5

2.0 for T ≥ 2.5

Determined by linear interpolation between 1 and 2

For structures in Seismic Design Category 4, the following equation is used for vertical seismic shear force (Section 1.4 and Section 11.7)

Fx = 0.01Wx (1.4-1)

where
Wx
=
dead load of structure at story " x "